Role 1 — Generator (three-phase only)
- The GEN port accepts a three-phase DG only, sized ≤ the inverter’s rated power (max input 10 / 12 / 15 kW at 15.2 / 18.2 / 22.8 A).
- Via the GEN port, the DG serves backup loads only. To also feed grid-side loads, connect the DG through an ATS on the grid side — the CT/meter is then mandatory.
- Never combine a DG with a grid-tied inverter on the same system — damage risk.
- The generator position must be correctly selected in the settings — a wrong selection can fail the system.
- G-V dry contact (16-pin block pins 8/9): voltage-free, wired to the DG’s NO start relay. Open = DG off; short = DG start. In Auto mode the DG starts at the ON SOC and stops at the OFF SOC; Manual mode gives a start/stop control.
Single-phase-DG homes cannot use the Kent G3 GEN port. Route such a DG through a grid-side
ATS — or the site belongs on the single-phase Kent platform. Raise it at survey, not at
commissioning.
Role 2 — AC-couple (retrofit PV inverter)
- The coupled grid-tied inverter must be three-phase and ≤ the hybrid’s rated power.
- Control is frequency-watt: set Max frequency = the PV inverter’s first-level over-frequency value + 0.1 Hz (confirm the PV inverter’s freq-watt response with its manufacturer first). At SOC ≥ 85 % the hybrid raises frequency to that value and stops the coupled inverter.
- Max Export Control (Based on Export Power & SOC): on a sustained export breach the smart-port relay opens.
Role 3 — Smart load
- Select Smart load output; choose On-grid always on (load powered whenever grid is present) or Off-grid always off; set the OFF and ON SOC/voltage thresholds that shed and restore the load on battery level — backup loads always win.
- Backup load + smart load together stay ≤ rated power.
Common mistakes
- A single-phase DG wired to the three-phase GEN port — discovered at the first outage.
- DG feeding grid-side loads through the GEN port instead of an ATS.
- Generator position not selected (or wrong) in settings after correct wiring.
- Max frequency guessed instead of matched to the coupled inverter’s over-frequency setting.