Role 1 — Generator (Three-Phase Only)
The GEN port accepts a three-phase DG only, sized at or below the inverter’s rated power.| Model | Max GEN input power | Max input current |
|---|---|---|
| Kent G3 10KW | 10 kW | 15.2 A |
| Kent G3 12KW | 12 kW | 18.2 A |
| Kent G3 15KW | 15 kW | 22.8 A |
Single-phase DG homes cannot use the Kent G3 GEN port. Route a single-phase DG through a grid-side ATS — or the site belongs on the single-phase Kent platform. Raise this at survey, not at commissioning.
Generator Wiring and Settings
- G-V dry contact (16-pin block, pins 8/9): voltage-free contact wired to the DG’s normally-open start relay. Open = DG off. Shorted = DG start.
- In Auto mode, the DG starts when SOC falls to the ON SOC threshold and stops when it reaches the OFF SOC threshold. Set both thresholds in the generator settings menu.
- In Manual mode, you start and stop the DG from the HMI.
- The generator position must be correctly selected in the inverter settings after wiring. A wrong or missing selection can prevent the system from operating correctly.
Role 2 — AC-Couple (Retrofit PV Inverter)
Confirm the coupled inverter is three-phase
The coupled grid-tied inverter must be three-phase and rated at or below the G3’s rated power.
Confirm frequency-watt response
Check with the PV inverter manufacturer that its frequency-watt response is active and confirm its first-level over-frequency trip value.
Set Max frequency
In the G3 settings, set Max frequency = the coupled inverter’s first-level over-frequency value + 0.1 Hz. At SOC ≥ 85%, the G3 raises frequency to this value and curtails the coupled inverter.
AC-couple export control behaviour is pending Kent validation. [KNB-VAL-10]
Role 3 — Smart Load
Select Smart load output in the GEN port settings, then configure:- On-grid always on — load is powered whenever the grid is present.
- Off-grid always off — load is shed during a grid outage.
- OFF SOC threshold — the battery level at which the smart load is shed.
- ON SOC threshold — the battery level at which the smart load is restored.
Common Mistakes
- A single-phase DG wired to the three-phase GEN port — discovered at the first grid outage.
- DG expected to feed grid-side loads through the GEN port alone instead of via an ATS.
- Generator position not selected or set incorrectly in settings after correct physical wiring.
- Max frequency value guessed instead of verified from the coupled inverter’s specification.