Before you start
Confirm which platform you are siting — clearance figures differ between Kent M1 and Kent G3. Never enclose either platform in a tight, unventilated cabinet or decorative box.Kent M1 clearances
The Kent M1 cools by natural convection — it is fanless and runs under 35 dB. Blocked convection means blocked cooling with no fan to compensate.| Direction | Minimum clearance |
|---|---|
| Above | ≥ 300 mm |
| Left | ≥ 300 mm |
| Right | ≥ 300 mm |
| Below | ≥ 500 mm |
The larger below-clearance (500 mm vs 300 mm sides) reflects the direction of natural convection airflow — warm air rises from the bottom of the unit. Do not obstruct the base zone with cable trays or conduit runs.
Kent G3 clearances
The Kent G3 uses fan-assisted cooling. Air enters on the left side of the unit and exhausts on the right side. Never block either side, and never position two units so the exhaust of one feeds directly into the intake of the other.| Requirement | Minimum clearance |
|---|---|
| To surrounding objects (all sides) | ≥ 300 mm |
| Between two Kent G3 inverters | ≥ 700 mm |
| Clear space in front of the unit | ≥ 500 mm |
| Bottom of unit above floor or ground | ≥ 500 mm |
Airflow direction — Kent G3
Sun and derating
Direct sunlight is a derating condition on both platforms. Output falls on the hot afternoons when the customer needs it most. Keeping the unit shaded is a performance requirement, not cosmetics. The Kent G3 heatsink can reach 75 °C during normal operation at high load. Brief the owner that the heatsink surface is a contact-burn hazard — never treat this as a fault condition.Ventilation don’ts
No sealed enclosures
No sealed niches, meter cupboards, or decorative boxes around the unit. Both platforms require open-air convection paths — even the fanless M1 needs free air movement.
No creeping obstructions
Curtains, creepers, and storage migrate into clearance zones over time. Photograph the clear zone at commissioning, tell the owner it must stay permanently clear, and note it in the handover record.
Common mistakes
Measuring clearance to the wall and then forgetting the shelf
Measuring clearance to the wall and then forgetting the shelf
The clearance zone must stay clear after the owner moves in. Brief the owner explicitly: nothing enters those zones, ever. Include a note in the handover documentation.
Stacking two G3 units 300 mm apart
Stacking two G3 units 300 mm apart
Some installers apply the 300 mm object rule to the gap between two inverters. That is wrong. The between-inverters minimum is 700 mm on Kent G3. This is the most common G3 multi-unit layout error.
Ignoring the 500 mm front-clearance on G3
Ignoring the 500 mm front-clearance on G3
The 500 mm front-clearance is a service-access requirement as much as a ventilation one. Covers that cannot open fully make every future service visit harder than it needs to be.