Questions
1. The universal Kent CT rule on both platforms is:- A. Arrow toward the loads, clamped anywhere convenient
- B. Arrow toward the grid, clamped at the grid connection point
- C. Arrow toward the inverter, on the backup feed
- D. Direction is irrelevant — software corrects it
- A. The platform default
- B. The DISCOM’s standard table
- C. The meter’s LCD
- D. The nameplate of the shipped CT — set exactly that, never assume
- A. A failing battery
- B. Wrong CT direction — the control loop is chasing itself
- C. Grid frequency drift
- D. A firmware bug
- A. A small negative Export calibration
- B. Turn the inverter off at high PV
- C. Doubling the CT ratio
- D. Selecting “No Meter”
- A. Solar Sell stays ON with Max sell power high
- B. Solar Sell OFF — and the zero-export witness test is mandatory before sign-off
- C. Remove the CT
- D. Only the meter setting matters
- A. Max export power is set to 0
- B. Allow Export is set to maximum
- C. Export settings are left at default
- D. The grid code is changed instead
- A. Extend it with matching twisted pair
- B. Extend it with any shielded cable up to 10 m
- C. Do not extend it — use the platform’s meter scheme instead
- D. Move the inverter
- A. CAN on pins 4/5
- B. WiFi pairing
- C. RS485 A/B per the pin map — polarity matters
- D. A current loop
- A. Live and neutral together
- B. The grid main live conductor only
- C. The earth conductor
- D. The backup feed
- A. A grid-code change
- B. Battery replacement
- C. Ignoring it — cosmetic only
- D. Checking the meter/CT communication and installation per the fault guidance
Answer key
- B
- D
- B
- A
- B
- A
- C
- C
- B
- D