Skip to main content
Ten questions from the CT, Meter & Zero Export group. Work through all ten before scrolling to the key. Suggested pass mark: 8 / 10. Each miss points to a source page — re-read it, not the whole group.

Questions

1. The universal CT placement rule on both Kent platforms is: clamp the CT around the:
  • A. Grid main live conductor only — arrow pointing toward the grid
  • B. Backup feed conductor — arrow pointing toward the loads
  • C. Live and neutral together — arrow in either direction
  • D. Earth conductor at the incomer

2. If you install a CT with the arrow pointing toward the loads instead of toward the grid, the most likely symptom is:
  • A. The system shuts down immediately
  • B. Erratic power readings with sustained or fluctuating export even under stable load conditions
  • C. The battery stops charging
  • D. E100 appears on the Kent M1

3. Clamping the CT around both live and neutral conductors together results in:
  • A. Double the correct reading — a 2× calibration error
  • B. A reading of 0 W — the equal and opposite currents cancel
  • C. A negative power reading
  • D. An overcurrent fault on the inverter

4. The CT ratio setting in the inverter must be taken from:
  • A. The platform’s factory default — it is pre-configured for the shipped CT
  • B. The DISCOM’s standard CT ratio table for the region
  • C. The nameplate of the specific CT shipped with the system — read it and set exactly that
  • D. The meter’s LCD display

5. On both Kent platforms, extending the CT signal lead with additional cable is:
  • A. Acceptable up to 10 m using shielded twisted-pair cable
  • B. Acceptable using any matching cable up to 5 m
  • C. Not permitted — if the lead does not reach, use the platform’s meter scheme instead
  • D. Acceptable if the cable resistance is below 2 Ω

6. On the Kent M1, when zero export is required, the Solar Sell setting must be:
  • A. ON, with Max Sell Power set to 0 W
  • B. OFF — and the zero-export witness test against the utility meter is mandatory before sign-off
  • C. Removed by deleting the CT entry
  • D. Set to the DISCOM’s published limit automatically

7. On the Kent G3 site with no feed-in permission, zero export is set by:
  • A. Setting Max Export Power to 0 in the grid settings
  • B. Setting Allow Export to maximum — the CT limits it physically
  • C. Leaving the export settings at factory default
  • D. Changing the grid code to a no-export variant

8. What does a short spike of export during a large load switch-off tell you about the zero-export setup?
  • A. The CT direction is reversed
  • B. The export limit value needs halving
  • C. Spikes on load switching are physics — they are not evidence of a zero-export failure; sustained export is the failure mode to investigate
  • D. The meter RS485 address is wrong

9. The Kent M1 E106 fault code relates to:
  • A. Battery undervoltage
  • B. CT abnormal — check CT installation, direction, and connection
  • C. Grid overvoltage
  • D. Fan failure

10. Zero-export control via the CT and inverter cannot control:
  • A. The battery discharge rate
  • B. The PV output on the Kent M1
  • C. Third-party grid-tied (GT) inverters on the same supply — they are invisible to the Kent system
  • D. The backup loads during an outage

Answer key

QAnswerWhy
1ACT on the grid main live conductor, arrow toward the grid. This applies to both Kent M1 and G3. Installing on a sub-circuit or with the arrow reversed both produce incorrect control.
2BA reversed CT causes erratic or persistently wrong power readings. The control loop chases the wrong signal, producing fluctuating display values and potential sustained export.
3BClamping around both L and N means equal and opposite currents cancel — the CT reads 0 W. The inverter sees no load and cannot control export.
4CAlways read the nameplate of the shipped CT and set that exact ratio. Never assume a default — the shipped CT ratio is confirmed on the nameplate only.
5CCT signal lead extensions are not permitted on either platform. If the lead cannot reach the grid connection point, use the platform’s smart meter scheme instead.
6BOn the Kent M1, Solar Sell OFF is the zero-export setting. The witness test against the utility meter is mandatory before the job is signed off.
7AOn the Kent G3, set Max Export Power to 0 in the grid settings. This is the correct zero-export configuration for a no-feed-in site.
8CBrief spikes on large load transitions are a physics effect — the inverter cannot respond in zero time. Sustained export is the indicator of a real zero-export failure.
9BE106 on the Kent M1 is a CT abnormal fault. Check the CT installation, direction, connection, and ratio setting.
10CThe Kent zero-export control loop only controls the Kent inverter’s own output. Third-party GT inverters on the same supply are invisible and will export independently.