What zero export actually does
The CT or meter at the grid connection reports any export to the inverter. The inverter responds by throttling PV output and steering surplus into the battery to hold export at the configured limit. When the limit is set to zero, the goal is zero sustained feed-in — but some physics apply:- Brief export blips on sudden load drops are normal. The loop measures, then reacts — there is always a short lag. A battery absorbing surplus is what turns those blips into near-zero behaviour in practice.
- The loop only sees what the CT sees. Every zero-export investigation starts at Direction & Location — a reversed or misplaced CT makes the loop chase the wrong number.
The two setting stacks — work from your platform’s page only
Parameter names differ completely between platforms. Using settings from the wrong platform’s guide is one of the most common commissioning errors.Kent M1
| Setting | Purpose |
|---|---|
| Solar Sell | Set to OFF for zero-export intent |
| Max sell power | Caps feed-in; requires a meter or CT connected |
| Sell offset | Compensates metering error — prevents anti-backflow from over-selling |
Kent G3
| Setting | Purpose |
|---|---|
| Allow Export | Set to OFF where feed-in is not permitted |
| Max export power | Set to 0 when Allow Export is OFF |
| Export calibration | −500 to +500 W; a small negative value backs off residual export to enforce true zero |
What zero export cannot guarantee
Control over third-party grid-tie inverters. An AC-coupled on-grid PV inverter with no comm link to the Kent hybrid keeps generating regardless of what the hybrid does. The Kent system can meter a third-party inverter’s output — it cannot throttle it. Survey any retrofit site for existing grid-tie generation and quote honestly about export behaviour. Zero blips. The difference between a fault and normal behaviour is the shape of the export trace. Momentary spikes on load steps are the loop working correctly. Sustained export above the limit is a fault. See the energy-flow test for pass criteria.The witness test is part of the configuration
No export-limited site is signed off on settings alone. With PV generating at a high level and site load minimised, the utility meter — not only the inverter display — must show no sustained export above the set limit. Run this test during a window that stresses the control loop, and capture the result. Procedure and pass criteria: Energy-Flow Test.Common mistakes
Configured in settings, never witnessed on the utility meter
Configured in settings, never witnessed on the utility meter
DISCOM penalties come from the utility meter reading, not the inverter display. The witness test is mandatory.
Settings copied from another brand's installation guide
Settings copied from another brand's installation guide
Parameter names on Kent platforms are exact and not interchangeable with other manufacturers’ menus.
Zero-export 'failure' that was a reversed CT the whole time
Zero-export 'failure' that was a reversed CT the whole time
A reversed CT makes the inverter throttle in the wrong direction — inverting import and export. Fix the CT physically first before investigating settings.
Promising zero export on a retrofit site with a third-party GT inverter on the grid side
Promising zero export on a retrofit site with a third-party GT inverter on the grid side
The Kent hybrid has no control channel to an uncoupled third-party inverter. Plan the metering and quote the limitation before signing the contract.