Skip to main content
Your goal is to confirm the inverter has permission to discharge and can see the site load correctly. Work through the checks in order — most “won’t discharge” calls are a reserve setting, a mode, or a TOU window doing exactly what it was configured to do. Symptom: the battery holds charge but never supports the load — the site imports from the grid with a full bank, day after day.

Check first

  1. Mode and thresholds — open the platform’s settings page. A reserve target or a hold mode is the first thing to rule out before any deeper diagnosis.
  2. Is the sensing right? If the CT or meter is misread, the inverter doesn’t know the house has a load to cover. Run the Energy-Flow Test direction check.
  3. Is SOC live and updating? Comms down can freeze the inverter’s discharge decisions — verify the SOC figure is changing.

Causes

CauseHow to confirmFix
Reserve or hold threshold reachedKent G3: SOC sits exactly at Battery reserve (default 80%) on-grid · Kent M1: Back Up mode holding its SOC targetWorking as designed — adjust the design values per the platform settings page if the customer’s intent differs
TOU window says idle or chargeSlot table on the platform settings page vs the inverter’s own clockCorrect the TOU windows or the RTC time per the platform settings page
Low-SOC cut-off reachedSOC at or below the platform’s overdischarge or shutdown thresholdLegitimate protection — let the bank recharge; revisit the reserve settings for backup-priority homes
Sensing wrong — inverter blind to the loadDirection test fails; load reads 0 W or signs are flippedFix per Wrong-CT Symptoms, then re-test discharge
Kent G3 ECO standbyPV under 100 W and SOC below the overdischarge point; unit in grid-standbyDesign behaviour — the pack recharges from grid or PV first before discharging
Discharge capped by the battery bankDischarge flatlines at (pack count × per-pack discharge limit) under large loadsDesign behaviour — check the pack count against the pairing matrix
BMS comms downSOC frozen; a comm alarm is present on the displayFollow the Comm Fault flow
“Inverter buys from grid with a full battery” is the highest-repeat complaint on hybrid sites. Walk mode → TOU → reserve → sensing in that order, demonstrate the corrected behaviour to the customer before you leave, and confirm the discharge is working on the display.

Escalate when

  • Configuration is verified correct, the sensing test passes, and the battery still never discharges — collect the settings snapshot and SOC/voltage readings and send to Kent service.
  • Discharge stops far above any configured threshold with BMS comms confirmed healthy.
Escalate to Kent New Energy service only — through your registered Kent partner channel or the Kent service desk details on your work order. Do not contact any third-party or component-manufacturer support line for a Kent-branded system: tickets outside the Kent channel are not tracked, not covered, and can void warranty handling.