Skip to main content
Most “battery not working” calls are a healthy system obeying its design. Learn the built-in reasons first; the fault-finding flows then start from the right place.

The bank’s own current limits

Every Kent battery model has a hard charge/discharge ceiling, and the bank’s total is packs × pack limit: A bank below the minimum-pack matrix runs the whole system at BMS-limited current — no fault shown, just less power both ways. That is design, not defect; the fix is pack count (or setting the inverter’s max currents to the bank’s real capability).

Thresholds that stop charge or discharge on purpose

Both platforms hold SOC thresholds that park the battery by design — the values and names are platform items, never carried across:
  • Kent M1Shutdown / Warn / Restart SOC govern low-battery behaviour; charging from the grid is disabled by default and must be deliberately enabled (with a max grid-charge current) on outage-first sites. Details: Kent M1 Settings Reference.
  • Kent G3Battery reserve stops on-grid discharge below its set point (default 80 %); Overdischarge and Force-charge SOC bound the low end; grid charging happens only where Allow grid charging permits. Details: Kent G3 Settings Reference.
  • TOU windows rule the clock on both platforms — a battery told to idle until 22:00 will. Slot logic and units differ per platform (that difference lives on the cheat card).
Kent G3 ECO function: with PV under 100 W and SOC below the overdischarge point, the inverter deliberately draws standby power from the grid instead of the battery — a protective behaviour, not a fault.

Dormant packs and wake-up

A deeply discharged pack drops into a dormant state and will not respond until woken — the official way, never by jump-charging:
  • Kent G3: the Battery Wakeup switch (professional Function Settings) wakes a dormant battery from PV or grid and charges it back above the overdischarge point.
  • Kent M1: Activate Bat provides the timed wake-up that prevents deep discharge on idle systems.
Pending Kent validation — do not configure in the field. [KNB-VAL-18] The Kent G3 manual’s printed wake-up voltage range is inconsistent with the platform’s battery window (documentation errata). Until Kent publishes the confirmed range: use the Battery Wakeup switch only, never key in wake-up voltage values from manual text, and leave voltage/time at factory values.
Pending Kent validation. [KNB-VAL-21] The Kent battery’s own pack-side wake procedure and front-panel indications are under confirmation with the Kent battery team. Until published here: wake a dormant bank through the inverter’s official function above; if the pack still does not respond, that is a Kent battery-service case — never jump-charge a pack from a bench supply or another battery.

Temperature protection

Charging and discharging are curtailed outside the pack’s temperature window and resume on their own when temperature normalises — on the Kent M1 the LCD flags these states explicitly (over-temperature and low-temperature protection codes). Persistent temperature blocks in a sensibly-sited system are an escalation, not a settings hunt.

Common mistakes

  • Selling a one-pack system as “full power” when the matrix says two — see the pairing matrix on the platform battery-wiring pages.
  • Leaving M1 grid-charge at its default (off) on a backup-first home — the battery is empty when the first cut comes.
  • Reading G3 reserve behaviour as a fault — on-grid discharge stops at the reserve by design.
  • Waking packs with improvised chargers instead of the platform’s official function.

When to escalate