The bank’s own current limits
Every Kent Lithium Battery model has a hard charge and discharge ceiling. The bank’s total capacity scales with pack count — adding packs multiplies current proportionally.| Battery model | Max charge current | Max discharge current |
|---|---|---|
| F1-5120 | 50 A | 60 A |
| F1-11780 | 115 A | 138 A |
| F1-16080 | 157 A | 188 A |
Thresholds that stop charge or discharge by design
Both platforms use SOC thresholds to protect the battery. The parameter names are platform-specific — never carry settings from one platform to the other.Kent M1
Shutdown / Warn / Restart SOC govern low-battery behaviour. Grid charging is disabled by default and must be deliberately enabled (with a max grid-charge current set) on outage-first sites. See Kent M1 Settings Reference for the full table.
Kent G3
Battery reserve stops on-grid discharge below its set point — the default is 80 %. Overdischarge and Force-charge SOC bound the low end. Grid charging only occurs where Allow grid charging is enabled. See Kent G3 Settings Reference for the full table.
Kent G3 ECO function: when PV is below 100 W and SOC is below the overdischarge setpoint, the inverter draws standby power from the grid instead of the battery. This is a protective behaviour built into the platform, not a fault.
Dormant packs and the official wake-up procedure
A deeply discharged pack drops into a dormant state and will not respond until woken. Never attempt to wake a dormant pack by jump-charging it from a bench supply or another battery.Kent G3: Battery Wakeup switch
The Battery Wakeup switch in the professional Function Settings menu wakes a dormant battery from PV or grid and charges it back above the overdischarge setpoint. Use this switch — do not key in wake-up voltage values from manual text.
Temperature protection
The battery automatically curtails charging and discharging outside its designed temperature window and resumes on its own when temperature returns to normal. On the Kent M1, the LCD displays explicit codes for over-temperature and low-temperature protection states. Persistent temperature blocks on a correctly sited system are an escalation — not a settings problem to hunt.Common mistakes
Quoting a one-pack system as 'full power' when the pairing matrix requires two
Quoting a one-pack system as 'full power' when the pairing matrix requires two
A single-pack bank is BMS-current-limited. Check the minimum-pack matrix on the platform battery-wiring pages before quoting.
Leaving Kent M1 grid-charge at its default (off) on a backup-first site
Leaving Kent M1 grid-charge at its default (off) on a backup-first site
The battery will be empty when the first grid outage arrives. Grid charging must be deliberately enabled on outage-first systems.
Reading Kent G3 reserve behaviour as a fault
Reading Kent G3 reserve behaviour as a fault
On-grid discharge stops at the Battery Reserve setpoint — 80 % by default. The battery is working correctly. Adjust the setpoint if a lower reserve is required.
Waking dormant packs with improvised chargers
Waking dormant packs with improvised chargers
A bench supply or a jump from another battery bypasses the BMS protection logic. Use only the platform’s official wake function.