Skip to main content
A wrong CT rarely announces itself — it makes the system look broken. This page maps each reading pattern back to the clamp.

The symptom map

What the display says

The platforms flag CT trouble differently — read your platform’s signal:
  • Kent M1: the LCD raises E106 (Meter or CT abnormal) — check direction, phase and cable continuity — and E107 (Meter or CT reverse connection) — check the CT wiring. An anti-backflow breach (often CT-rooted) raises E105.
  • Kent G3: there is no dedicated CT alarm for a reversed clamp — the tell is the fast-fluctuating power pattern above and wrong flow on the screen; the source manual’s FAQ sends you straight to the CT arrow.

The fix order — physical, then settings, then re-test

  1. Location — grid connection point, live conductor only.
  2. Direction — arrow toward the grid.
  3. Phase mapping (Kent G3) — CT, conductor and terminals all matching.
  4. Ratio — exactly the shipped CT’s nameplate. [KNB-VAL-08]
  5. Only now touch orientation settings (M1 Meter CT orientation / G3 Forward–Reversal), and only to state the physical truth.
  6. Re-run the Energy-Flow Test — a CT fix without the live test is a guess.

Common mistakes

  • “Fixing” a reversed clamp with the Reversal setting when the clamp is right there — physical first; software direction is for CTs that genuinely cannot be re-clamped now.
  • Swapping settings for an hour when the load reads 0 W — that one is always the L+N clamp.
  • Declaring the CT fine because the sign is right at noon — with PV masking import, the sign proves nothing; test grid-on/PV-off.
  • Blaming the battery for “discharging to grid at night” — flipped CT, nine times in ten.

When to escalate