Skip to main content
A wrong CT rarely announces itself with a clear error — instead it makes the system look broken in ways that waste hours of settings investigation. This page maps each reading pattern back to the clamp so you can go straight to the right fix.

The symptom map

What you see on the displayWhat it meansFix
Import/export signs flipped; battery discharging to the gridCT reversed, or on the wrong conductorFix physically per Direction & Location; re-run the live test
Load reads 0 W with loads clearly runningCT clamped around both live and neutral — magnetic fields cancelRe-clamp on the live conductor only
Power wrong by a large factor (e.g. 10× or ÷10)CT ratio setting does not match the clampRead the ratio from the shipped CT nameplate and set exactly that value
Fast, continuous power fluctuation with steady loadsCT direction wrong — the control loop is chasing itselfVerify arrow toward grid; run the live test to confirm
One phase imports while another discharges simultaneouslyCT-to-phase mismatch on a three-phase installationRe-map per Meter & Phase Matching
Phantom import or export, noisy small readings with no load changesExtended or damaged CT lead picking up noiseRestore the design-length lead; do not extend CT leads
Export logic not responding; grid figures frozenCT lead open-circuit or RJ45/terminal connection unseatedContinuity check and reseat per the platform CT page
SOC frozen on the inverter displayNot a CT fault — comm link is downGo to Cable Checks

What the display tells you by platform

The platforms signal CT trouble differently. Read your platform’s indicator first: Kent M1: the LCD raises specific fault codes for CT problems.
CodeMeaningStarting action
E106Meter or CT abnormalCheck direction, phase mapping, and cable continuity
E107Meter or CT reverse connectionCheck CT wiring direction
E105Anti-backflow breachOften CT-rooted — check CT before export settings
Kent G3: there is no dedicated alarm for a reversed CT. The tell is the fast-fluctuating power pattern in the symptom table above and wrong flow shown on the energy screen. The source manual’s FAQ sends you directly to the CT arrow as the first action.

The fix order — physical, then settings, then re-test

Work this sequence in order. Skipping ahead wastes time.
1

Location

Confirm the CT is at the grid connection point on the live conductor only. Nothing else is the correct position.
2

Direction

Confirm the arrow is toward the grid on every CT. Physically re-clamp if it is reversed.
3

Phase mapping (Kent G3)

Confirm CT, conductor, and terminal leads all match on each phase — L1 with L1, L2 with L2, L3 with L3.
4

Ratio

Confirm the ratio in settings matches exactly what is printed on the shipped CT’s nameplate.
5

Software orientation — only now

If a software setting needs updating to reflect the corrected physical install, set it now: M1 Meter CT orientation, G3 Forward / Reversal. Only set these to describe the physical truth — never to paper over a physical error.
6

Re-run the Energy-Flow Test

A CT fix without the live test is a guess. Run all three tests in Energy-Flow Test and record the results.
Do not use the G3 Reversal setting to fix a clamp that is physically right there and can be re-clamped. Physical correction is always the right move when the CT is accessible.

Common mistakes

If the CT is accessible, re-clamp it. The software setting is a last resort for a CT that genuinely cannot be reached — not a shortcut.
Zero-watt load with loads clearly running is always a live-and-neutral clamp. It has no settings fix. Re-clamp on the live conductor only.
With PV generating, solar output can mask import and make a reversed CT look correct. Test condition is always grid ON, PV OFF.
A flipped CT sign makes the control loop drive the battery to compensate for a false export reading. The battery is obeying the control — the CT is the fault.