Check first
- Occasional or chronic? A one-off alarm during a known grid disturbance self-clears by design — no action needed. A daily or hourly pattern requires measurement data before any action.
- Measure at the inverter’s AC terminals across the problem window — the terminal voltage, not the DB board voltage, is what the inverter sees. One hour of readings across the problem period tells you far more than a single spot measurement.
- Terminations tight? Loose or undersized AC terminations mimic an out-of-band grid at every load step. Check these before concluding the grid is the problem.
Causes
| Cause | How to confirm | Fix |
|---|---|---|
| Genuine grid excursion (transient) | Alarm self-clears; terminal voltage is normal when measured | None needed — the inverter reconnects automatically when the grid returns to the acceptable range |
| Chronically out-of-band grid | Logged terminal readings are out of the code’s window at peak hours | DISCOM case: Kent compiles the evidence and leads the utility-consent process; do not adjust protection values unilaterally |
| Loose or undersized AC connection | Voltage sags at the inverter terminals under load steps; heat marks at terminations | Re-terminate and torque per the platform AC wiring page; re-measure across a full day |
| Wrong grid code selected | Commissioning record vs the Kent parameter sheet for the site’s DISCOM | Set the grid code from the Kent parameter sheet only |
| No grid detected | Kent M1: E100 · Kent G3: NO-Grid; upstream breaker off or phase dead | Restore the AC path — follow Not Starting |
| Unbalanced or distorted grid (Kent G3 only) | G-PHASE / GRID-INTF02 class alarms appear alongside measurements | Confirm the grid quality and the AC cable run; one restart; if persistent, escalate |
Alarm names differ between platforms. Kent M1 uses E101 (grid voltage) / E102 (grid frequency) / E108 (other grid abnormalities). Kent G3 uses the OV-G-V / UN-G-V / OV-G-F / UN-G-F alarm families. The triage is the same — record the exact alarm string, letter-for-letter, before doing anything else.
Escalate when
- The grid is chronically out of band on logged terminal measurements — Kent leads the DISCOM process; bring the readings, timestamps, and photos.
- Grid alarms persist on a site with a verified-healthy grid and tight terminations — this is a service case.
- Any request arrives to “just widen the limits” — that path runs through utility consent and Kent, or it does not happen.
Escalate to Kent New Energy service only — through your registered Kent partner channel or the Kent service desk details on your work order. Do not contact any third-party or component-manufacturer support line for a Kent-branded system: tickets outside the Kent channel are not tracked, not covered, and can void warranty handling.