Skip to main content
Ten questions from the Troubleshooting group. Work through all ten before scrolling to the key. Suggested pass mark: 8 / 10. Each miss points to a source page — re-read it, not the whole group.

Questions

1. The correct restart discipline when a fault code appears on either platform is:
  • A. One restart; if the fault persists, stop and escalate to Kent service
  • B. Restart repeatedly until the code clears or 30 minutes have passed
  • C. Never restart — escalate immediately without any restart attempt
  • D. Three restarts, ten minutes apart, then escalate

2. The correct power-off sequence before any service work is:
  • A. Turn off the grid AC breaker first, then the battery
  • B. Turn off the battery switch first, then the grid AC — the exact reverse of power-on
  • C. Turn off the PV DC switch first, always
  • D. Any order is acceptable once the display is dark

3. A Kent M1 showing E400–E402 or a Kent G3 showing “CAN Fail” with SOC missing — the first check is:
  • A. Check the battery cells for physical damage
  • B. Check the BMS communication cable — label, continuity, pinout, and RJ45 seating — before touching any setting
  • C. Update the inverter firmware
  • D. Check the grid code setting

4. Kent G3 “BatName-FAIL” means:
  • A. The battery pack is empty — recharge before commissioning
  • B. The BMS fuse has blown
  • C. The battery selection in the HMI is wrong — correct it after the comm cable is confirmed good
  • D. The inverter firmware needs updating

5. Kent M1 E303 (AFCI) fault behaviour is:
  • A. Permanent lockout — a service call is always required to clear it
  • B. Clears only after a full battery reset and 24-hour wait
  • C. Auto-recovers; if it occurs 5 times in one day it auto-clears — check the AFCI CT connection if the code repeats
  • D. A cosmetic fault that can be ignored

6. Grid protection points — voltage and frequency trip thresholds — should be changed:
  • A. By the installer to match the nearest available grid code
  • B. By the customer from the display if tripping seems too frequent
  • C. Automatically by the meter when grid conditions change
  • D. Only per the Kent-issued parameter sheet for the specific DISCOM — never improvised or estimated

7. A backup circuit that trips the backup output breaker under load is best resolved by:
  • A. Widening the backup breaker’s trip setting
  • B. Moving the overloaded load to the grid-only panel — backup overload means something too big is on the essential panel
  • C. Increasing the inverter’s rated power via a setting
  • D. Replacing the backup breaker with a higher-rated type

8. Kent M1 fault code E100 means:
  • A. PV string overvoltage
  • B. Battery undervoltage — check the pack SOC
  • C. No AC connection — restore the AC path: upstream breaker, terminations, cable
  • D. Fan failure

9. Kent M1 E303 (AFCI) occurs up to 5 times per day without intervention. Before diagnosing further, you should check:
  • A. The PV string Voc against the 500 V limit
  • B. The AFCI CT connection and installation at the PV input
  • C. The battery SOC level
  • D. The grid frequency setting

10. An internal fault code — Kent M1 E600–E602 or Kent G3 INI-FAULT / DSP-B-FAULT — that survives one restart is:
  • A. A site wiring problem — check terminations before escalating
  • B. Fixed by a factory reset from the advanced menu
  • C. Fixed by swapping the BMS communication cable
  • D. A Kent service case — stop all work, do not open the unit

Answer key

QAnswerWhy
1AOne restart is the maximum field step. If the fault survives a single restart, the job is an escalation — not more cycling. Repeated restarts obscure fault data.
2BPower-off is the reverse of power-on: battery off first, then grid AC. This sequence protects the inverter from back-feeding and protects the battery from an uncontrolled disconnect.
3BA BMS comm fault is almost always a cable problem. Check the crossover cable label, continuity, pinout, and RJ45 seating before touching any setting or firmware.
4CBatName-FAIL means the battery selection in the HMI does not match the connected pack. Correct the selection to PYLON_LV (for Kent Lithium Battery) after confirming the comm cable is good.
5CE303 auto-recovers and clears itself after 5 occurrences in a day. If it repeats, investigate the AFCI CT connection at the PV input — it is not a hard fault requiring a service call by itself.
6DGrid protection points are utility-consent settings. Use only the Kent-issued parameter sheet for the site’s specific DISCOM. Improvised changes risk grid disconnection or regulatory violation.
7BBackup overload means something too large is on the essential panel. The fix is to move that load to grid-only — not to widen the trip point or upsize the breaker.
8CE100 is “No AC Connection.” Check the upstream AC breaker, the AC wiring terminations, and the cable path before looking elsewhere.
9BWhen E303 repeats, check the AFCI CT connection and installation at the PV input. A loose or incorrectly installed AFCI CT is the most common cause of repeat E303 events.
10DInternal fault codes that survive a restart are Kent service cases. Do not open the unit, do not attempt a factory reset — escalate with the fault code, time, and one restart record.