What every field-relevant Kent G3 setting does, and the Kent rules around it. This page covers the G3 only — parameter names and units differ between the G3 and the Kent M1. Do not carry settings from one platform to the other.
For trained and authorized installers only. The professional menu is password-locked and partner-gated. Grid protection levels load from the grid code — never edit them manually.

Storage Modes

Modes are exclusive — one at a time. Off-grid also engages automatically on a grid outage and supplies backup loads only.
ModeLoad prioritySupply priority
Self-useload → battery → gridPV → battery → grid → DG
Selling firstload → grid → batteryPV → battery → grid → DG
Off-gridload → batteryPV → battery → DG

Mode Options

SettingWhat it does
Allow ExportEnables feed-in in Self-use. Leave OFF where feed-in is not permitted.
Max export powerCaps feed-in (default 1.1× rated). If feed-in is not allowed, set this to 0.
Export calibration−500 to +500 W (default 20 W). Trim slightly negative to eliminate residual export shown by the utility meter.
Battery reserve5–95%, default 80%. Below this level the battery stops discharging during on-grid operation.
Allow grid chargingGrid charges the battery when SOC falls to Force-charge SOC, or when PV cannot meet the set current in a charge window.
Unbalanced outputON = each phase feeds its own load; one phase can carry up to 50% of total power (15 kW unit → up to 7.5 kW on one phase). OFF = power is split equally at rated/3 per phase.
Grid peak shavingCaps grid draw at the set value by reducing battery charging. Exceeded only to keep the load alive. Set to the site’s sanctioned import limit.
Pending Kent validation. [KNB-VAL-06]The firmware default for unbalanced output and the 150% unbalanced-load figure are under bench confirmation. Until published here: do not promise more than 100% of the per-phase rating on any single phase. Record the per-phase test result at commissioning.

Time of Use (TOU)

Up to 6 charge windows and 6 discharge windows. Each window sets:
  • A current value in amperes (not watts — this is the critical difference from the Kent M1)
  • A SOC or voltage cut-off
  • An enable toggle per window
TOU is available in Self-use and Selling first modes. Grid charges during charge windows only when Allow grid charging is also ON.
TOU windows on the G3 are current-based (amperes), not power-based (watts). Crews carrying M1 habits will set the wrong values. Double-check before leaving the site.

Battery Settings and Functions

SettingDefaultNotes
Max charge currentPer bank sizingSet to packs × pack current limit
Max discharge currentPer bank sizingSet to packs × pack current limit
Overdischarge SOC20%Battery stops discharging below this level
Recovery SOCAbove overdischargeBattery resumes discharge once it recovers to this level
Force-charge SOC10%Grid charges battery when it falls to this level
Max charge SOC100%Upper charging limit
Ordering rule: Force-charge SOC < Overdischarge SOC < Recovery SOC. Violating this order causes unexpected charge or discharge stops with no obvious fault code.
When PV is under 100 W and SOC is below the overdischarge threshold, standby power draws from the grid rather than the battery. Reduces unnecessary shallow cycles during overcast days.
After a prolonged period at low SOC, the system charges to the Healing SOC before allowing discharge again. This restores SOC measurement accuracy. Normal behaviour — not a fault.
Pending Kent validation — leave battery wake-up at factory values. [KNB-VAL-18]The battery wake-up voltage range printed in the source manual does not match this platform’s 40–60 V battery window — this is a known documentation errata. Until Kent publishes the confirmed range: use the Battery Wakeup switch only. Do not key in any wake-up voltage values from manual text.

Zero-Export Recipe

Use this sequence on any export-limited site:
1

Disable export

Set Allow Export = OFF, or set Max export power = 0 where the DISCOM requires an explicit numerical cap.
2

Trim calibration

Set Export calibration slightly negative if a residual export is visible on the utility meter after step 1.
3

Witness test

With high PV and minimum load running, watch the utility meter for any sustained export. Then step a heavy load and confirm CT sign is correct. Photograph the result. 📷

Only-PV-Power-Load

This feature is OFF by default and auto-disabled when PV voltage exceeds 510 V. If the load exceeds available PV power, the load shuts off. Auto-restart retries at 3 minutes, then 5 minutes, then 10 minutes. After the third failed restart, a manual reset is required. Know this behaviour exists before spending time chasing what looks like a mystery shutdown.

Common Mistakes

  • Feed-in “disabled” by hope alone instead of Allow Export OFF plus Max export power 0 plus a witness test.
  • TOU windows set in watts by M1 habit — this platform’s windows are current-based in amperes.
  • Battery reserve dropped to 20% “for more savings” — the first grid outage lands on a nearly empty battery.
  • Wake-up voltage values typed from manual text instead of using the switch only — see the validation warning above.