What the CT is for
A current transformer (CT) clips around a grid conductor and reports the current flowing through it. The inverter uses that signal to determine whether the site is importing or exporting, and by how much. That information drives:- Self-use logic — directing PV and battery to cover the load before buying from the grid
- Zero-export control — throttling PV output when the site would otherwise export
- Energy display figures — grid import, export, and load values on the screen and the app
The clamp rule
- The CT clamps around one conductor: the live. Clamping around the live and neutral together cancels the magnetic fields — the CT reads 0 W and the control logic goes completely blind.
- Close the clamp until it clicks fully shut. A half-latched CT under-reads consistently and the fault is nearly invisible until someone moves the cable.
- Where the CT sits and which way its arrow faces are separate disciplines — both are covered on Direction & Location.
Ratio discipline
The CT reports a scaled-down version of the conductor current. The ratio setting tells the inverter the scale factor. A wrong ratio means every power figure on the display is wrong by a large factor — and export limits are enforced against numbers that have nothing to do with the actual grid flow.Lead length — the quiet killer
The CT’s output is a millivolt-class analog signal. Long or improvised lead extensions pick up electrical noise, and that noise reads as phantom import or export that the control loop continuously chases.- The Kent G3 box kit ships with a 1 m, 2.3 mm² CT lead — that is the design lead length for that kit.
CT scheme vs meter scheme
Both Kent platforms can sense the grid either directly with CTs on the conductor, or through a supported energy meter that carries its own CTs and communicates over RS485 to the inverter. You choose one scheme per site — not both.On the Kent G3, if CTs are connected directly, a separate smart meter is not required for grid sensing. The platform-specific wiring options are on the Kent M1 CT & Meter and Kent G3 CT & Meter pages.
Common mistakes
CT clamped around live and neutral together
CT clamped around live and neutral together
The magnetic fields cancel. Load reads 0 W and all control logic is blind. Reclamp on the live conductor only.
CT ratio entered from memory instead of the nameplate
CT ratio entered from memory instead of the nameplate
Ratios vary by CT model and SKU. Always read it off the physical CT you installed.
CT lead extended with random cable 'just two metres'
CT lead extended with random cable 'just two metres'
Even a short extension on an analog millivolt signal introduces noise. Use the meter scheme if the lead cannot reach.
Half-latched clamp that never audibly clicked
Half-latched clamp that never audibly clicked
The CT under-reads until disturbed. Always confirm the click before closing up the enclosure.