Skip to main content
The CT is the hybrid system’s eyes on the grid connection. Every smart function — self-use, export limiting, and the energy figures on the display — is only as accurate as the clamp on that one conductor. Get this right and the system controls correctly; get it wrong and the symptoms can look like an inverter fault.
For trained and authorised installers only. Isolate the AC conductor before clamping anything around it.

What the CT is for

A current transformer (CT) clips around a grid conductor and reports the current flowing through it. The inverter uses that signal to determine whether the site is importing or exporting, and by how much. That information drives:
  • Self-use logic — directing PV and battery to cover the load before buying from the grid
  • Zero-export control — throttling PV output when the site would otherwise export
  • Energy display figures — grid import, export, and load values on the screen and the app
Without a healthy CT signal, none of these functions work correctly. The system has no reliable way to know what is happening at the meter.

The clamp rule

  • The CT clamps around one conductor: the live. Clamping around the live and neutral together cancels the magnetic fields — the CT reads 0 W and the control logic goes completely blind.
  • Close the clamp until it clicks fully shut. A half-latched CT under-reads consistently and the fault is nearly invisible until someone moves the cable.
  • Where the CT sits and which way its arrow faces are separate disciplines — both are covered on Direction & Location.

Ratio discipline

The CT reports a scaled-down version of the conductor current. The ratio setting tells the inverter the scale factor. A wrong ratio means every power figure on the display is wrong by a large factor — and export limits are enforced against numbers that have nothing to do with the actual grid flow.
Pending Kent validation. [KNB-VAL-08] The shipped CT scheme and ratio per Kent SKU are under confirmation. Until published here: read the ratio from the shipped CT’s nameplate and enter exactly that value — never assume a default. On the Kent G3, the box-kit CT and the meter-scheme CT carry different ratios; the kit table is on the Kent G3 CT & Meter page.

Lead length — the quiet killer

The CT’s output is a millivolt-class analog signal. Long or improvised lead extensions pick up electrical noise, and that noise reads as phantom import or export that the control loop continuously chases.
  • The Kent G3 box kit ships with a 1 m, 2.3 mm² CT lead — that is the design lead length for that kit.
Pending Kent validation. [KNB-VAL-23] The approved CT lead extension method per Kent SKU is under confirmation. Until published here: do not extend CT leads. If the supplied lead cannot reach the grid connection point, use the platform’s meter scheme instead — never a spliced-on length of flex.

CT scheme vs meter scheme

Both Kent platforms can sense the grid either directly with CTs on the conductor, or through a supported energy meter that carries its own CTs and communicates over RS485 to the inverter. You choose one scheme per site — not both.
On the Kent G3, if CTs are connected directly, a separate smart meter is not required for grid sensing. The platform-specific wiring options are on the Kent M1 CT & Meter and Kent G3 CT & Meter pages.

Common mistakes

The magnetic fields cancel. Load reads 0 W and all control logic is blind. Reclamp on the live conductor only.
Ratios vary by CT model and SKU. Always read it off the physical CT you installed.
Even a short extension on an analog millivolt signal introduces noise. Use the meter scheme if the lead cannot reach.
The CT under-reads until disturbed. Always confirm the click before closing up the enclosure.