Skip to main content
Ten questions from the Safety group. Work through all ten before scrolling to the answer key. Suggested pass mark: 8 / 10. Each miss points to a specific source page — re-read that page, not the whole group.

Questions

1. After powering an inverter fully OFF, how long must you wait before opening any cover or touching internal conductors?
  • A. 30 seconds — the display going dark is the signal
  • B. 5 minutes — timed, regardless of display state
  • C. 15 minutes — only for battery work
  • D. No wait is needed if the PV DC switch is open

2. The Kent G3 PV DC switch may only be operated when the string current is below:
  • A. 5 A
  • B. 2 A
  • C. 0.5 A
  • D. Any value — the switch is rated for full load

3. Who may open an inverter enclosure to work on internal parts?
  • A. Any licensed electrician on site
  • B. The installing technician, provided the 5-minute discharge wait has passed
  • C. Nobody in the field — there are no user-serviceable parts inside; internal work is Kent service only
  • D. The customer, for dust cleaning using a dry cloth

4. During normal operation, the Kent G3 heatsink surface can reach approximately:
  • A. 45 °C
  • B. 60 °C
  • C. 75 °C
  • D. 95 °C

5. The correct power-OFF sequence on both Kent platforms is:
  • A. The exact reverse of power-on — battery side off first, grid AC last
  • B. Grid AC off first, then battery
  • C. PV DC switch first, always
  • D. Any order, as long as the display is dark before disconnecting battery

6. PPE must be worn:
  • A. Only during battery terminal work
  • B. Only when the inverter is energised and running
  • C. Throughout the entire installation process, from arrival to sign-off
  • D. Only during AC termination work at the DB

7. For battery work specifically, the manual’s footwear and hand protection rule is:
  • A. Cotton gloves are sufficient for low-voltage packs
  • B. Rubber shoes and insulating gloves
  • C. Standard site safety boots are adequate
  • D. No specific rule — follow general site PPE

8. Grid protection points — voltage and frequency trip settings — may be changed:
  • A. By the installer whenever the local DISCOM supply seems unstable
  • B. Freely, if export readings look wrong
  • C. Once per season to match seasonal voltage profiles
  • D. Only with utility consent, by authorized personnel, using the Kent-issued parameter sheet

9. After completing the labelled 5-minute discharge wait, and before touching any conductor, you must also:
  • A. Tap the terminals with an insulated tool to check for spark
  • B. Meter-verify that no dangerous voltage remains on the relevant conductors
  • C. Wait a further 5 minutes as an additional buffer
  • D. Nothing further — the timed wait alone is sufficient per the manual

10. The Kent rule for the earth-pit resistance reading at every installation site is:
  • A. Measure the earth resistance and photograph the reading; escalate poor soil to Kent before energising
  • B. Assume the builder’s earth is adequate for a residential installation
  • C. Only measure on commercial or industrial sites
  • D. Quote the manual’s reference figure to the customer as the confirmed site resistance

Answer key

QAnswerWhy
1BThe manual specifies a 5-minute wait after full power-off before opening any cover. The display state is not the trigger.
2CThe 0.5 A arc-prevention rule applies to the Kent G3 DC switch. Operating under load risks a DC arc.
3CNeither platform has user-serviceable parts inside. Opening the enclosure in the field is not permitted — internal work is Kent service.
4CThe Kent G3 heatsink can reach 75 °C during operation. Do not touch the heatsink during or shortly after operation.
5APower-off is the exact reverse of power-on: battery (and any GEN source) off first, then grid AC.
6CPPE applies throughout the entire installation process, not only at specific steps.
7BThe manual’s battery safety instructions specify rubber shoes and insulating gloves for battery work.
8DGrid protection points are utility-consent settings. They are never adjusted freely by the installer or by improvisation.
9BAfter the discharge wait, verify dead with a meter before touching conductors. The wait alone is not a substitute for measurement.
10AMeasure and photograph the earth-pit reading at every site. Escalate poor soil results to Kent before energising — never assume the builder’s earth is adequate.