Skip to main content
Good earthing is the difference between protection devices that work and expensive decoration. This page is the overview; exact conductor sizes and torques live on each platform’s installation pages.
For trained/authorized installers only.

Protective earth (PE) — first on, last off

  • Connect the inverter’s PE before any AC or DC wiring, and remove it last.
  • Kent M1 — dual PE is mandatory. Both the AC-connector system ground and the chassis protective-earth point must be connected — never only one. Use 10 mm² outdoor single-core copper and paint-seal the chassis earth terminal after fitting. The Backup-port PE must be grounded or backup will not operate in a grid failure.
  • Kent G3 — connect the external grounding conductor and the heat-sink grounding terminal per the manual figure; copper conductor recommended.
  • PV module frames are earthed to the array earth per IS 3043 practice; PV+/PV− conductors are not earthed on these transformerless platforms — platform pages carry the specifics.

System earthing overview — figure KNB-SVG-12; site example KNB-PH-05

The earth pit

Measure pit resistance with a proper earth tester at every site, photograph the reading, and log it on the commissioning checklist. Poor or unmeasurable earth = stop and fix before energizing.
Pending Kent validation. [KNB-VAL-14] Kent’s published earth-resistance limit is under confirmation. Until published here: measure and photograph the reading at every site, do not attribute any specific ohm figure to the manual, and escalate poor-soil sites to Kent before energizing.

Surge protection (SPD)

Kent requires external Type II SPDs on both the AC and DC sides on Indian sites regardless of built-in protection — the surge and lightning profile demands it. Check SPD health flags at every service visit.

RCDs

  • Kent M1: residual-current monitoring is built in; external Type A RCDs are supported — grid side 100-300 mA recommended.
  • Kent G3: RCD selection and the backup-side scheme follow the platform installation page.
  • The approved backup-side RCD scheme for both platforms is tied to the N-E behaviour item — see the validation block on Electrical Basics [KNB-VAL-04].

Common mistakes

  • Connecting one Kent M1 PE point and calling it done — both are mandatory, and backup will not run in an outage without the Backup-port PE.
  • Landing the SPD earth on a paint-covered bracket bolt — SPDs need a real, low-impedance earth.
  • Skipping the pit measurement because “the building has earthing” — measure, photograph, log.

When to escalate