Check first
- Spikes or sustained export? Momentary blips on load steps are the control loop’s normal response physics. Sustained export above the limit is the fault. Establish the trace shape before anything else.
- CT live test — with grid ON and PV OFF, the display must read import. A reversed or misplaced CT is the number-one cause of apparent export. Run this before touching settings.
- Third-party grid-tie inverter on site? If another GT inverter is connected upstream of the Kent unit’s CT, its generation is uncontrollable by the Kent hybrid — this is an expectations case, not a settings case.
Causes
| Cause | How to confirm | Fix |
|---|---|---|
| CT reversed / wrong location / wrong phase | Energy-Flow Test fails — display reads export at night or with PV off | Physical fix per Wrong-CT Symptoms, then re-witness the export limit |
| Export settings incomplete or misconfigured | Settings audit against the platform commissioning page | Kent M1: Solar Sell must be OFF for zero-export intent; set Max sell power and Sell offset per design (witness test is mandatory before sign-off) · Kent G3: set Allow Export per design; set Max export power = 0 where no feed-in is permitted; use a small negative Export calibration to eliminate residual trickle |
| Residual trickle export | Small steady export at high PV with correct CT and settings | Kent G3: apply a small negative Export calibration per the manual · Kent M1: use Sell offset to compensate the metering error |
| CT ratio wrong | Power figures are off by a large consistent factor | Set ratio exactly per the shipped CT nameplate — never assume the ratio |
| AC-coupled third-party GT inverter | Export continues with the Kent unit fully curtailed; confirmed by site survey | Physics — not a configuration fix; reset expectations and involve Kent for the compliance design |
| Blips misread as sustained export | Trace shows spikes only on load steps with no sustained export | Explain per Zero Export — The Concept; battery absorption in progress narrows these blips |
Close it properly
A zero-export fix is only closed when you have completed the witness test against the utility meter: PV generation high, site load minimised, no sustained export above the configured limit, result photographed into the commissioning record. 📷 Configuration without a utility-meter witness is not a closed ticket.Escalate when
- Sustained export persists with the CT proven correct and settings verified — send the settings snapshot and an export trace to Kent service.
- A DISCOM dispute is open — escalate to Kent with the commissioning record and witness evidence. The compliance response runs through Kent, not through the installer.
Escalate to Kent New Energy service only — through your registered Kent partner channel or the Kent service desk details on your work order. Do not contact any third-party or component-manufacturer support line for a Kent-branded system: tickets outside the Kent channel are not tracked, not covered, and can void warranty handling.