Skip to main content
Your goal is to find why the Backup port isn’t sustaining the essential loads and fix the root cause before the next outage. The leading cause is a load that exceeds the platform’s backup rating. Symptom: the grid fails and the essential loads go dark — or the backup trips within seconds of every outage.
For trained and authorized installers only. Simulated-outage testing opens live breakers with the customer’s loads connected — brief the customer before you start.

Check first

  1. What was on the backup at the moment of failure? Compile the peak load history with the customer. One appliance too many is the leading cause.
  2. Battery state at the time — an empty bank or one parked by a reserve threshold has nothing to give. If the battery is the issue, go to Battery Not Discharging first.
  3. Which device tripped — the inverter’s own alarm, the backup MCB, or an RCD? An RCD trip points to Nuisance Tripping.

Causes

CauseHow to confirmFix
Backup overloadedKent M1: E202 (off-grid overload) / E405 (battery output overload) · Kent G3: Over-Load / OV-ILLC; clamp-meter during load steps confirmsMove heavy loads to the grid side; resize the essential panel per Essential Loads
Motor start exceeds backup capabilityTrips only when a compressor or pump starts — not under steady loadKent M1: size to rated power only — no motor-start surge headroom is promised · Kent G3: overload capability is 2× rated for 10 s — verify the real inrush fits within this window
Battery empty or parked by thresholdSOC was at cut-off when the outage hitReview the reserve strategy on the platform settings page; enable grid-charge deliberately on outage-priority homes
One phase overloaded (Kent G3 only)Trip correlates with a single heavy phase; other phases are lightly loadedRebalance loads across all three phases; per-phase limit applies — do not promise more than 100% of per-phase rating on any single phase
Loads drop on transfer then returnSensitive loads reset at every outageThe pass criterion is “loads ride through” — verify with the black-start test; do not quote a millisecond figure for Kent M1
Grid supply landed on the Backup portWiring trace; history of “worked once then died” after a grid outageInstallation fault with hardware consequences — isolate immediately and escalate; never re-energise as-is
Backup voltage faultKent M1: E200 (output V high) / E201 (output V low)E201 usually means the source is exhausted (PV + battery low); check energy state and settings per the alarm guidance

Prove the fix

Re-run the black-start test with the real essential loads: open the grid breaker, confirm loads ride through the transfer, verify a clean reconnect when grid returns, and confirm no RCD trips. Photograph the display during backup operation and log the measured backup load. 📷

Escalate when

  • Overload trips repeat with a measured load that is inside the platform’s rated backup current.
  • You have any suspicion the grid supply ever reached the Backup port.
  • Transfer behaviour remains erratic after all of the causes above are cleared.
Escalate to Kent New Energy service only — through your registered Kent partner channel or the Kent service desk details on your work order. Do not contact any third-party or component-manufacturer support line for a Kent-branded system: tickets outside the Kent channel are not tracked, not covered, and can void warranty handling.