Pre-power checklist
Complete all five items before you close any breaker:- Siting correct — no direct sun on the unit, no flammables nearby, serviceable, adequate ventilation space.
- PE wire, DC cables, AC cables, and comm cables all connected correctly with terminals firm.
- Cables tied, routed without interference, insulation undamaged throughout.
- Unused AC/DC and communication ports are blocked off.
- AC voltage and frequency at the grid connection point meet grid-connection requirements.
Power ON — the M1 sequence
Power OFF is the exact reverse: step 5 → step 1, battery first. For any service power-off, follow the Isolation & Shutdown procedure and wait the labelled 5 minutes before opening any enclosure.
First-run configuration — in this order
On first commissioning the LCD prompts you through these settings. Complete them in sequence:Configure meter / CT
Set CT orientation to towards the grid. Set CT ratio exactly per the nameplate on the shipped CT. [KNB-VAL-08]
Select grid standard
Select the safety code for your jurisdiction, then press “Setting” to confirm. The button must show “OK” — if it does not, the selection has not taken effect. Set only per the Kent parameter sheet. [KNB-VAL-01]
Set operation mode
Select the mode for the site design: Self Use, Sell First, Back Up, or Custom. See Kent M1 Settings Reference.
LCD navigation basics: ESC = back, Up/Down = page scroll, hold ENTER for 5 seconds = LCD reset. Screen timeout defaults to 2 minutes; brightness adjustable 10–100 %. Parameter changes require cancelling “Lock out all change” in Basic Setting first — this requires the partner-gated password.
Function tests before sign-off
Run every test below before leaving site:Battery both ways
Force a charge cycle and a discharge cycle. Confirm currents are within the platform limits and within the installed pack limits.
CT sanity check
Grid on, PV off → display must show import. Energise a heavy load and confirm the sign and magnitude respond correctly. 📷
Backup transition
Open the grid breaker with real essential loads running. Loads must ride through. Do not quote or promise a specific transition time in milliseconds. [KNB-VAL-03]
Zero-export witness
On export-limited sites: high PV, low load, watch the utility meter confirm no feed-in to the grid. [KNB-VAL-07] — settings on the Settings Reference page.
Derating awareness: direct sun on the unit, high ambient temperature, an output-percentage cap setting, over-frequency grid events, and high input voltage or current all derate output by design. Check these conditions before suspecting a hardware fault on a site that “isn’t producing enough.”
Common mistakes
- Powering battery-first because “that’s how all inverters work” — the Kent M1 is AC-first ON, battery-first OFF.
- Skipping the “Setting → OK” confirmation on the grid code — the selection does not take effect without that confirmation.
- Leaving site without a full parameter screenshot set archived against the unit serial number.