Before you start
- System commissioned to the point of a live display.
- CT or meter physically installed per Direction & Location.
- A known heavy single-phase load identified and available — kettle, geyser, iron-class (per phase on the Kent G3).
- Eyes on both the inverter display and the utility meter.
Test 1 — CT Direction (convention-proof)
This test proves the CT is at the right location and pointing the right way without relying on anyone’s remembered arrow convention.Confirm import on the display
The inverter display must show the site importing from the grid. With no PV and real loads running, import is the only correct reading.
Step the heavy load
Switch on the high-current load. The grid import figure on the display must rise by the load’s approximate wattage, and the sign must remain import.
Test 2 — Per-Phase Mapping (Kent G3 only)
Run Test 2 only after Test 1 passes. This test confirms that each CT is on the correct conductor and connected to the correct terminal pair.Step a known load on L1 only
Switch on a load you are certain is single-phase on L1. Use a single-phase socket on the L1 circuit — not a multi-phase outlet.
Confirm only L1 responds
The L1 reading on the display rises. L2 and L3 stay flat. Photograph the display.
Test 3 — Zero-Export Witness (export-limited sites)
This test is mandatory on all export-limited sites, and specifically required on Kent M1 sites before sign-off [KNB-VAL-07]. Configure all export settings before running it.
Set the conditions
Pick the hardest available window: PV generating at a high level, site load minimised. This maximises the surplus the control loop must manage.
Watch the utility meter — not only the inverter display
Monitor the utility meter for several continuous minutes. Include the moment of a sudden load drop (switch off a load mid-test) to stress the loop’s reaction time.
Evaluate the export trace
Brief momentary blips on load steps are expected and acceptable — that is the loop reacting. Sustained export above the configured limit is a fail.
Record it
Each test result needs a line in the commissioning record:| Test | Condition | Reading / result | Photo ref |
|---|---|---|---|
| Test 1 — Direction | Grid ON, PV OFF | Import: ___ W | 📷 |
| Test 2 — Per-phase (L1) | L1 load stepped | L1 rise: ___ W, L2/L3 flat | 📷 |
| Test 2 — Per-phase (L2) | L2 load stepped | L2 rise: ___ W, L1/L3 flat | 📷 |
| Test 2 — Per-phase (L3) | L3 load stepped | L3 rise: ___ W, L1/L2 flat | 📷 |
| Test 3 — Zero-export | PV high, load low | Max sustained export: ___ W | 📷 |
Common mistakes
Running Test 1 with PV generating
Running Test 1 with PV generating
PV output can mask the import and make the sign look correct even when it is not. The test condition is grid ON, PV OFF.
Watching the inverter display for Test 3
Watching the inverter display for Test 3
DISCOM penalties are based on the utility meter reading. Watch the utility meter for Test 3 — not the inverter screen.
Using a multi-phase outlet for the per-phase load step
Using a multi-phase outlet for the per-phase load step
A multi-phase outlet loads more than one phase simultaneously. Use a confirmed single-phase socket for each per-phase step.
Passing Test 1 and skipping Test 2 on a three-phase site
Passing Test 1 and skipping Test 2 on a three-phase site
CT direction correct, phases crossed is still a wiring fault — it just fails silently on a lightly loaded site.