Before you start
- System commissioned to the point of a live display; CT/meter physically per Direction & Location.
- A steppable heavy load identified (geyser, iron, kettle-class) — per phase on Kent G3.
- Eyes on both displays: the inverter’s screen and the utility meter.
The energy-flow witness test: grid on, PV off must read import — figure KNB-SVG-16
Test 1 — Direction (convention-proof)
- Grid ON, PV OFF (DC switch open), battery idle.
- The display must show import — the house drawing from the grid.
- Step the heavy load: the grid figure rises, same sign.
Test 2 — Per-phase mapping (Kent G3)
- With Test 1 passed, step the known load on L1 only — the display’s L1 figure responds, L2/L3 stay flat.
- Repeat for L2, then L3.
Test 3 — Zero-export witness (export-limited sites)
- Export settings configured per the platform page (Kent M1 · Kent G3).
- Pick the harshest window available: PV high, site load minimised.
- Watch the utility meter — not only the inverter display — through several minutes of that condition, including a sudden load drop.
Record it
Each test gets a line in the commissioning record: condition, reading, photo. The settings snapshot then freezes the configuration these tests proved.Common mistakes
- Testing with PV on — solar masks the import and the sign proof evaporates.
- Watching the inverter display for Test 3 — the DISCOM reads the utility meter, so do you.
- Per-phase test with the load on a multi-phase outlet — use a known single-phase load.
- Passing Test 1 and skipping Test 2 on a three-phase site — direction right, phases crossed still fails silently.