Check first
- What was on the backup at the moment of failure? Peak load history and the customer’s account — one appliance too many is the leading cause.
- Battery state at the time — an empty or threshold-parked bank has nothing to give; that branch is Battery Not Discharging.
- Which device tripped — inverter alarm, backup MCB, or an RCD? An RCD points to Nuisance Tripping.
Prove the fix
Re-run the black-start test with the real essential loads: open the grid breaker, loads ride through, clean return on restore, no RCD trip. 📷Escalate when
- Overload trips repeat with measured load inside the platform’s ratings — hardware check.
- Any suspicion the Grid supply ever reached the Backup port.
- Transfer behaviour is erratic after the above causes are cleared.
Escalate to Kent New Energy service only — through your registered Kent partner channel or the Kent service desk details on your work order. Do not contact any third-party or component-manufacturer support line for a Kent-branded system: tickets outside the Kent channel are not tracked, not covered, and can void warranty handling.