Skip to main content
Symptom: the energy-flow screen contradicts reality — export at night, zero PV in full sun, load at 0 W with the house running, battery arrows pointing the wrong way.

Check first

  1. Which reading is impossible, exactly? One wrong figure implicates its sensor; all of them wrong implicates the sensing chain at the grid point.
  2. Cross-check against physical truth — utility meter, a clamp meter, the sun.
  3. Any alarm alongside? A flow oddity plus an alarm string is that alarm’s flow first.
Displays report; they rarely lie on their own. A wrong flow is almost always a wrong input — CT, meter or comms — not a wrong screen. Fix the sensing, and the picture fixes itself. If a reading stays impossible after the sensing chain is proven, capture photos and escalate rather than reinterpreting the screen.

Escalate when

  • A physically-proven sensing chain still yields an impossible reading.
  • Flow anomalies coincide with internal-fault codes — the code’s flow leads.